● Standard:IEC61008-1
● Structure: Pure electromagnetic type with compact construction and fewer internal components. No auxiliary power supply needed.
● Environmental Adaptability: Switch performance will not be affected by ambient temperature and lightning interference.
● Working Principle: Equipped with mutual inductor to detect vector differential value of passing current. When the residual current reaches or exceeds the rated leakage operating current, the secondary winding outputs power to activate the tripper and cut off the faulty circuit instantly.
● Protection Performance: Current-operated fast leakage protector, rapidly disconnects fault circuits to avoid personal injury and electric fire accidents.
| Standard | IEC/EN 61008 | |
| Electrical features | Mode | Electro-magnetic type,electronic type |
| Type(wave form of the earth leakage sensed) | A,AC | |
| Rated current In | 16,25,32,40,63A | |
| Poles | 2P,4P | |
| Rated voltage Ue | AC 230/400V | |
| Rated sensitivity I△n | 0.01,0.03,0.1,0.3,0.5A | |
| Insulation voltage Ui | 500V | |
| Rated residual making and breaking capacity I△m | 630A | |
| Short-circuit current I△c | 6000A | |
| Rated frequency | 50/60Hz | |
| SCPD fuse | 6000A | |
| Pollution degree | 2 |
| Standard | IEC/EN 61009 | ||
| Mechanical features | Electrical life | 4000 | |
| Mechanical life | 10000 | ||
| Protection degree | IP20 | ||
| Ambient temperature(with daily averages≤35°C) | °C | -25~+40 | |
| Storage temperature | °C | -25~+70 | |
| Installation | Terminal connection type | Cable/U-type busbar/Pin-type busbar | |
| Terminal size top for cable | mm² | 35 | |
| AWG | 18-3 | ||
| Terminal size top for busbar | mm² | 35 | |
| AWG | 18-3 | ||
| Tightening torque | N*m | 2.5 | |
| In-Ibs | 22 | ||
| Mounting | On DIN rail EN 60715(35mm) by means of fast clip device | ||
| Connection | From top and bottom |