1.This product features an LED display that shows real-time grid voltage and current values.
2.Protection parameters-including overvoltage, undervoltage, overcurrent, and time delay can be configured locally. The device also includes a configuration menu and functionssuch as one-touch restoration to factory settings. When the product is in the "No Output"(OFF) state, press and hold the ON/OFF button for 5 seconds to restore factory settings.
3.The product also possesses rapid disconnection capabilities; when the overvoltage level reaches 320V or the undervoltage level drops to 110V, the device automatically enters rapid disconnection mode, cutting off the load within 0.1 seconds.
| No. | Option code | Option | Max | Min | Default | Step | Unit | Description |
| 1 | P-1 | Power-on delay | 999 | 1 | 5 | 1/10 | S | |
| 2 | P-2 | Recovery delay | 999 | 1 | 30 | 1/10 | S | |
| 3 | P-3 | Overvoltage | 300 | 230 | 270 | 1/10 | V | OFF: Close over voltage |
| 4 | P-4 | Undervoltage | 210 | 140 | 170 | 1/10 | V | OFF: Close under voltage |
| 5 | P-5 | Voltage trip time | 10.0 | 0.1 | 0.5 | 0.1/1.0 | S | |
| 6 | P-6 | Overcurrent | 63 | 1.0 | 63.0 | 0.1/1.0 | A | OFF :Close over current |
| 7 | P-7 | Current trip time | 10.0 | 0.1 | 5 | 0.1/1.0 | S | |
| 8 | P-8 | Continuous overcurrent counting | 20 | 0 | 0 | 1 | Times | OFF: Turn off counting |
| 9 | P-9 | Automatic reset | on | off | on | on: Self recovery | ||
| OFF: Manual recovery | ||||||||
| 10 | P-10 | Setup lock password | 999 | 000 | 112 | 1/10 | When this value is not 112, you can only view the parameter and cannot set it |
⚫ Front-face panel
| Parameter | Specification |
| Rated Voltage | 220V |
| Rated Current | 40A/63A/80A/100A |
| Rated Frequency | 50/60 Hz |
| Maximum phase voltage | 350V |
| Over/Under voltage recovery | hysteresis 5V |
| Inductive Load | 6KW (Motor type) |
| Resistive Load | 13KW (Electric heating and lighting) |
| Power Consumption | <2W |
| Ambient Temperature | -25℃ to 65℃ |
| Humidity | <95% |
| Installation Method | DIN Rail Mounting |
| Overvoltage Setting | 230V-300V, adjustable in 1V steps |
| Undervoltage Setting | 140V-210V, adjustable in 1V steps |
| Overcurrent Setting | 1A-63A, adjustable in 1A steps |
| Delay Setting | 1s-999s, adjustable in 1s steps |
| Display Accuracy | Voltage 1V |
| Current | 0.1A |
⚫ Wiring diagram / Dimensional Drawing
⚫ Setup menu