1. Scope of application and main uses
KYN28-24 switchgear has various functions to prevent misoperation, including preventing the trolley from moving with load, preventing the grounding switch from closing the circuit breaker when it is closed,preventing the grounding switch from being closed with electricity, and preventing mistakenly entering the live compartment.
KYN28-24 switchgear is equipped with ZN73 series mid-mounted high-voltage AC vacuum circuit breaker and solid-sealed vacuum switch with excellent performance. The secondary circuit of the switchgear is equipped with advanced and reliable control and protection components; The bus is insulated by heat shrinkable insulation material or epoxy coating, the electrode shape is optimized,and the cabinet structure is compact. KYN28-24 switchgear is a power distribution equipment with advanced technology, stable performance, reasonable structure, easy use, safety and reliability.
2.Product reference standards
a.GB1984 High Voltage AC Circuit Breaker
b.GB3906 3~35KV AC metal enclosed switchgear
c.Common technical reguirements of GB/T11022 standards for high-voltage switchgear and control equipment.
d.DL/T404 Indoor AC high voltage switchgear ordering technical conditions
e.DL/T593 Technical guidelines for common ordering of high voltage switchgear
3.Use environmental conditions
● Normal use conditions
a.Ambient temperature: maximum temperature: + 40°C, minimum temperature:-15 °C, and the average value measured within 24 hours does not exceed 35 °C.
b.Humidity conditions are as follows:
-the average daily relative humidity does not exceed 95%;
-the average daily water vapor pressure does not exceed 2.2 kpa: the average monthly water vapor pressure does not exceed 1.8 kpa;
Condensation occasionally occurs under such conditions;
c.The altitude does not exceed 1000m;
d.the ambient air is not significantly contaminated by dust, smoke, corrosive and/or combustible gases,vapors or salt spray;
e.Vibration or ground motion from outside the switchgear and control equipment is negligible;
f.The magnitude of electromagnetic interference induced in the secondary system does not exceed 1.6KV.
● Special conditions of use
When used under normal environmental conditions exceeding the specifications of GB/T11022, the company and users can negotiate and reach an agreement on special operating conditions exceeding the normal operating conditions.In order to prevent condensation, the switchgear is equipped with a heater. When the switchgear is in standby state, it should be put into use. When the switchgear is operating normally, attention should also be paid to putting the heater into operation.
1.Main technical parameter to see below table
| No. | Name | Unit | Parameter | ||||
| 1 | Rated voltage | kV | 24 | ||||
| 2 | Rated frequency | Hz | 50/60 | ||||
| 3 | Rated insulation level | 1min power frequency withstand voltage (effective value) | kV | Interphas to ground | 60 | Insulation Fracture |
79 |
| Lightning impulse withstand voltage (peak value) | kV | 125 | 145 | ||||
| Power frequency withstand voltage of auxiliary control circuit | V | 2000 | |||||
| 4 | Rated current | A | 630、1250、1600、2000、2500 | ||||
| 5 | Rated short-circuit breaking current | kA | 20 | 25 | |||
| 6 | Rated short-time closing current (peak value) | kA | 50 | 63 | |||
| 7 | Rated short-time withstand current (4s) | kA | 20 | 25 | |||
| 8 | Rated peak value withstand current | kA | 50 | 63 | |||
| 9 | Rated voltage of auxiliary control circuit | V | DC or AC 110/220 | ||||
| 10 | Protection grade | IP4X (Circuit breaker doors open or isolate compartment IP2X) | |||||
| 11 | Overall dimension (W×D×H) | mm | 800×1810×2380 | 1000×1810×2380 | |||
| 12 | Weight | kg | 840~1440 | ||||
Note: The depth of the overhead inlet and outlet cabinet is 2360mm.
2.Main technical parameter of ZN73-24 Vacuum circuit breaker
| No. | Name | Unit | Parameter | ||
| 1 | Rated voltage | kV | 24 | ||
| 2 | Rated insulation level | 1min power frequency withstand voltage (effective value) | kV | 60 | |
| 2 | Lightning impulse withstand voltage (peak value) | kV | 125 | ||
| 3 | Rated frequency | Hz | 50/60 | ||
| 4 | Rated current | A | 630、1250、1600、2000 | 630、1250、1600、2000、2500、3150 | |
| 5 | Rated short-circuit breaking current | kA | 20 | 25 | |
| 6 | Rated short-time closing current (peak value) | kA | 50 | 63 | |
| 7 | Rated short-time withstand current (4s) | kA | 20 | 25 | |
| 8 | Rated peak withstand current | kA | 50 | 63 | |
| 9 | Rated single capacitor bank breaking current | kA | 630 | ||
| 10 | Rated back-to-back capacitor bank breaking current | V | 400 | ||
| 11 | Rated short circuit breaking current breaking cycles | cycles | 50 | ||
| 12 | Mechanical life | cycles | 20000 | ||
| 13 | Rated operating sequence | 0-0.3s-CO-180s-CO | |||
3. Technical parameters of spring operating mechanism
| No. | Name | Unit | Parameter | |
| 1 | Rated operation voltage | Closing tripping coil | V | AC220、AC110、DC220、DC110 |
| Opening tripping coil | ||||
| 2 | Working current | Closing tripping coil | A | AC 220 or DC 220:1.1 AC 110 or DC 110:3.1 |
| Opening tripping coil | ||||
| 3 | Energy storage motor power | W | 80、110 | |
| 4 | Energy storage motor Voltage | V | AC220、AC110、DC220、DC110 | |
| 5 | Motor energy storage time | S | ≤10 | |